Scroll To Top

Quad 600V URD – P7328D-AG

Home   »   AgWire   »   Quad 600V URD – P7328D-AG
Direct Burial Power Quad 600V URD Cable

Quad 600V URD – P7328D-AG

Insulation

CROSS-LINKED POLYETHYLENE XLP

Conductors

ALUMINUM

Sizes

#4 - 500 MCM

Share it

Secondary power distribution up to 600V in areas with soft soils where rodents are not present.

Used for secondary distribution and underground service at 600 volts or less, either direct burial or in ducts, in areas with soft soils where rodents are not present.

Secondary power distribution up to 600V in areas with soft soils where rodents are not present

Conductors are stranded, compressed 1350-H16/H26 aluminum insulated with vulcanized interlinked polyethylene. Neutrals are triple yellow extruded stripe. Neutrals have sequential footage markers. Conductors are durably surface printed for identification. Three phase conductors and one neutral conductor are cabled together to produce the quadruplex cabled together to produce the quadruplex cable configuration.

Paige’s quadruplex or paralleled 600 volt secondary UD cable meets or exceeds the following applicable ASTM specifications.

  • B-231 Aluminum 1350 Conductors. Concentric-Lay-Stranded
  • B-609 Aluminum 1350 Round Wire. Annealed and Intermediate Tempers, for Electrical Purposes.
  • B-786 19 Wire Combination Unilay-Stranded Aluminum Conductors for Subsequent Insulation.

Paige’s quadruplex 600 volt secondary UD cable meets or exceeds all applicable requirements of ICEA S-105-692 for cross-linked polyethylene insulated conductors and UL Standard 854 for Type USE-2.

CODE WORD PHASE CONDUCTOR NEUTRAL DIAMETER (mils) WEIGHT PER 1000 FOOT (lbs.) ALLOWABLE AMPACITANCE
Size (AWG) Stranding Insulation Thick (mils) Size (AWG) Stranding Insulation Thick (mils)  Single Pase Conductor  Complete Cable Direct Burial In Ducts
 QUADRUPLEX WITH YELLOW EXTRUDED STRIPE NEUTRAL
 Tulsa 4 7 60 4 7 60 346 833 255 120 85
Dyke 2  7 60 4 7 60 403 973 342 155 115
 Notre Dame 1/0 19 80 2 7 60 512 1236 534 200 150
Syracuse 2/0 19 80  1 19 60 555 1340 657 225 170
 Wake Forest 4/0 19 90 2/0 19 80 653 1589 974 290 225
Rust 250 26 80 3/0 17 80 702 1695 1124 320 225
Slipperyrock 350 37 95 4/0 19 80 831 2006 1544 385 305
Wofford 500 37 95 350 30 95 980 2366 2179 465 370
±Ampacity 90°C conductor temperature 20°C ambient, RHO 90, 100% load factor for three conductor triplex with neutral carrying only unbalanced load.