Products AgWireCopper UF 600VAC

Copper UF 600VAC

P7295D-AG
Legacy:
Product Type

Direct Burial Control

Gauge Size

#14 - 4/0

Conductors

2 or 3

Jacket

PVC

Voltage

600

Insulation

PVC

Temperature

60°C WET OR DRY

Description
Type TC Control Cable meets or exceeds the applicable requirements of the following standards and specifications: ASTM – (All applicable standards) NFPA 70 (NEC) UL 1581 Electrical Wires, Cables & Flexible Cords ICEA S-58-679 – Control Cable Conductor Identification Method 1, Table 2 UL 1685 – UL Flame Exposure Test (70,000 Btu/hr)
Construction

Conductors: (for Multiconductor cables only): Sizes 14,12 & 10 AWG: Solid,annealed bare copper per ASTM B-3,UL-493, and UL-719 Sizes 8 & 6AWG: Concentric, compressed stranded (class B)

Conductors: (for Single Conductor cable only): Sizes 14-8AWG: Solid,annealed bare copper ASTM B-3 and UL-493 Sizes 6-4/0AWG: Concentric compressed stranded (class B)ASTM B-3 and UL-493

Insulation: (for Multiconductor cables only): Polyvinyl chloride (PVC). UL-493 and UL-719

Ground Wire: For 2 or 3 conductor cable with ground. Solid, annealed bare copper per ASTM B-3. Sizes as follows:

INSULATED CONDUCTORSINSULATED CONDUCTORS
SIZESIZENOM O.D.
AWGAWGAWG
UF60°C60°C
*NMC-B60°C60°C

Cable Assembly: Multiconductor cables are assembled flat parallel. For cables with ground, the ground wire is placed between two of the insulated conductors.

Overall Jacket: (integral jacket and insulation for single conductor cable) Sunlight, moisture and fungus-resistant. Gray PVC. UL-493 and UL-719.

Color Code: Two-conductor cable: Black, White Three-conductor cable: Black, White, Red

Surface Print: Single Conductor Cable: Ink print on jacket “(size) AWG Type UF 600 Volts Sunlight Resistant (UL)” Multiconductor Cable with Ground: Ink print on jacket “(size) AWG/(# of conds.) W.G.Type UF 600V Sunlight Resistant(UL)” Multiconductor Cable w/o ground: Ink print on jacket “ (size) AWG/(#of conds.)

Application

600 VAC underground feeder circuit cable for powering single phase or three phase limited power loads and control circuits for remote irrigation systems or remote electrical equipment, like irrigation wells,

Use: UL Listed and OSHA acceptable. In accordance with Articles 336 and 339 of the Nat’l Electrical Code (and subject to local code requirements), Type UF cables may be used for underground feeder or branch-circuit wiring for installation above or below ground, including direct burial, and in wet or corrosive locations. Multi-conductor Type UF (Type NMCB) cables may also be used for exposed or concealed interior wiring in wet, dry or corrosive locations and in cable trays. This cable powers single phase or three phase limited power loads and control circuits for remote irrigation systems or remote electrical equipment, like irrigation wells.