Products AgWireCopper Tray Cable

Copper Tray Cable

P7267D-AG
Legacy:
Product Type

Direct Burial Power

Conductors

2, 3 or 4

Jacket

PVC

Voltage

600

Insulation

HIGH DIELECTRIC PVC

Temperature

90°C DRY, 75°C WET

Description
Secondary power distribution up to 600V available in conduit or direct burial with or without ground wire.
Construction

Conductors: Bare, soft annealed copper per ASTM B-3 SIZES 8 THROUGH 2 AWG Concentric stranded, class B (7 strands) ASTM B-8 and UL-83 table 4.1 SIZES 250 THROUGH 500MCM Concentric stranded, class B (37 strands) ASTM B-8 and UL-83 table 4.1,

Insulation: HIGH DIELECTRIC POLYVINYL CHLORIDE UL-83 table 13.1 (THWN 75°C) UL-83 table 14.1 (THHN 90°C) THICKNESS UL-83 table 21.5 Insulation Armor: NYLON UL-83 paragraph 35.1 THICKNESS UL-83 table 21.5,

Insulation Armor: NYLON UL-83 paragraph 35.1 THICKNESS UL-83 table 21.5,

Cable Assembly: SIZES 8 THROUGH 4/0 AWG Three or more conductors are assembled round with fillers as needed. A tape binder is applied over the assembly. Two conductors are assembled flat parallel (round, with fillers as needed, is available upon request.) SIZES 250 THROUGH 750 MCM Conductors are assembled round with fillers as needed. A tape binder is applied over the assembly.,

Ground: 1 bare cop

Application

This specification covers two, three and four conductor cables having VW-1 THHN/ THWN (PVC/Nylon) conductors with an overall polyvinyl chloride (PVC) jacket, conforming to Article 318 “Cable Trays” and Article 340 “Power and Control Cable Type TC” of the 1981 National Electrical Code, and Subject 1277 of Underwriters Laboratories, inc. Meets the requirements of the 70,000 BTU “Cable Tray Propagation Test” per IEEE-383 and shows reserve capabilities by also passing the 210,000 BTU flame test. Rated 600 volts, 90°C dry and 75°C wet.,

Use: UL listed and OSHA acceptable. Recognized for use in Class 1, Division 2 hazardous locations and for installation in trays, wireways, troughs, channels, ducts, and conduit. Specifically approved for direct burial, wet or dry locations and outdoors in cable trays where a sunlight resistant rating is required. Designed to supply power to motors, or for connection to other power devices. Deep well submersible pump.